ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 421202 - Intrinsic Safety Barrier - Control Device
This K-System intrinsic safety barrier, identified as KFD2-CD-EX1.CN, provides galvanic isolation and signal conditioning for controlling field devices in hazardous areas. It functions as a switch amplifier, interfacing digital control signals from the safe area with intrinsically safe loads such as solenoid valves or alarms in classified hazardous locations. Engineered for process automation, chemical, and oil & gas industries requiring robust safety integrity.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Intrinsic Safety Barrier, Control Device
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 24 VDC nominal (20.4 VDC to 28.8 VDC operating range)
- OUTPUT TYPE: Single channel, intrinsically safe switched output
- OUTPUT PARAMETERS: Uo = 10.6 V, Io = 50 mA, Po = 130 mW (for Ex ia IIC applications)
- INTERFACE/CONTROL:
- INPUT: Digital control signal from safe area, typically 24 VDC
- OUTPUT: Drives solenoid valves, alarms, or other switching loads in hazardous areas
- ENVIRONMENTAL/MOUNTING:
- HAZARDOUS AREA CERTIFICATION: Ex ia IIC T4 Ga (for Zone 0, 1, 2 applications)
- SAFETY INTEGRITY LEVEL (SIL): Up to SIL 2 (IEC 61508)
- OPERATING TEMPERATURE: -20 °C to +60 °C
- MOUNTING: 35 mm DIN rail mount
- ENCLOSURE PROTECTION: IP20
- COMPATIBILITY/APPLICATION:
- APPLICATION: Interfacing control systems with intrinsically safe solenoid valves, alarms, and indicators in process industries
- ISOLATION: Galvanic isolation between input, output, and power supply circuits