ОПИСАНИЕ ПРОДУКТА
SCHNEIDER ELECTRIC 48211 - Contactor
This device is an electromechanical switching apparatus from the TeSys D series, engineered for robust control of electrical loads in industrial environments. It facilitates the remote switching of three-phase AC motors and resistive loads, integrating into motor control centers, power distribution panels, and automation systems requiring reliable load interruption and connection. Its design emphasizes durability and operational stability for demanding applications.
Technical Specifications:
- SERIES/FAMILY: TeSys D
- COMPONENT TYPE: Contactor
- ELECTRICAL SPECS:
- RATED OPERATIONAL CURRENT (AC-3): 12 A at <= 440 V AC
- RATED OPERATIONAL CURRENT (AC-1): 25 A at <= 690 V AC
- RATED OPERATIONAL VOLTAGE (POWER CIRCUIT): 690 V AC 50/60 Hz
- COIL VOLTAGE: 24 V DC
- NUMBER OF POLES: 3P
- MOTOR POWER (AC-3): 3 kW at 220/230 V AC, 5.5 kW at 380/400 V AC, 5.5 kW at 415 V AC, 5.5 kW at 440 V AC, 7.5 kW at 500 V AC, 7.5 kW at 660/690 V AC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6 kV
- RATED INSULATION VOLTAGE (Ui): 690 V (power circuit), 600 V (signaling circuit)
- MECHANICAL/PHYSICAL:
- AUXILIARY CONTACTS: 1 NO + 1 NC (standard configuration)
- MECHANICAL ENDURANCE: 15 Mcycles
- ELECTRICAL ENDURANCE: 2 Mcycles (AC-3 at Ue <= 440 V)
- INTERFACE/CONTROL:
- CONTROL CIRCUIT TYPE: DC low consumption
- TERMINALS: Screw clamp terminals
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (front face)
- OPERATING TEMPERATURE: -5 to 60 degrees C
- STORAGE TEMPERATURE: -60 to 80 degrees C
- MOUNTING STYLE: DIN rail or screw fixing
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Motor control, resistive load switching, power distribution, HVAC systems, pumping stations, conveyor systems.
- COMPATIBILITY: Compatible with TeSys D thermal overload relays, auxiliary contact blocks, and surge suppressors.