SCHNEIDER ELECTRIC A9A15215 - Miniature Circuit Breaker
The SCHNEIDER ELECTRIC A9A15215 is a Miniature Circuit Breaker from the Acti 9 iC60N series, engineered for overcurrent and short-circuit protection in low-voltage electrical distribution systems. It integrates a thermal-magnetic trip unit to safeguard circuits against overload and fault conditions, making it suitable for industrial, commercial, and residential applications requiring compliance with IEC/EN 60898-1 and IEC/EN 60947-2 standards.
Technical Specifications:
- SERIES/FAMILY: Acti 9 iC60N
- COMPONENT TYPE: Miniature Circuit Breaker (MCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 15A
- POLES: 1P+N (1 Pole + Neutral)
- TRIPPING CURVE: C-curve
- NOMINAL OPERATIONAL VOLTAGE (Ue): 230V AC (phase-neutral), 400V AC (phase-phase)
- NOMINAL INSULATION VOLTAGE (Ui): 500V AC
- NOMINAL IMPULSE WITHSTAND VOLTAGE (Uimp): 6kV
- BREAKING CAPACITY (Icn): 6kA at 230V AC (IEC/EN 60898-1)
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- NUMBER OF MODULES: 2 (18mm width)
- TERMINAL TYPE: Tunnel terminals
- WIRE CAPACITY: 1 to 25 mm² (flexible), 1 to 35 mm² (rigid)
- INTERFACE/CONTROL:
- TRIP UNIT TECHNOLOGY: Thermal-magnetic
- INDICATORS: Trip indicator, position indicator (ON/OFF)
- ENVIRONMENTAL/MOUNTING:
- MOUNTING TYPE: DIN rail (35mm symmetrical)
- IP RATING: IP20 (terminals), IP40 (front face in enclosure)
- OPERATING TEMPERATURE: -35°C to +70°C
- STORAGE TEMPERATURE: -40°C to +85°C
- POLLUTION DEGREE: 3
- COMPATIBILITY/APPLICATION:
- APPLICATION: Overcurrent protection, short-circuit protection
- TARGET SYSTEMS: Industrial control panels, commercial distribution boards, residential electrical installations
- STANDARDS: IEC/EN 60898-1, IEC/EN 60947-2