ОПИСАНИЕ ПРОДУКТА
SCHNEIDER ELECTRIC LV848752 - Air Circuit Breaker
The SCHNEIDER ELECTRIC LV848752 is a MasterPact MTZ2 series air circuit breaker designed for robust low voltage power distribution and protection in industrial and commercial installations. This device integrates advanced Micrologic X trip unit technology for precise overcurrent, short-circuit, and ground fault protection, alongside comprehensive energy management and communication capabilities. It is engineered for critical applications requiring high breaking capacity and reliable operational continuity, such as main incomers, sub-distribution boards, and motor control centers.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 2000A
- NUMBER OF POLES: 4P
- OPERATIONAL VOLTAGE (Ue): 690V AC (maximum)
- INSULATION VOLTAGE (Ui): 1000V AC
- IMPULSE WITHSTAND VOLTAGE (Uimp): 12kV
- BREAKING CAPACITY (Icu): 66kA at 400/415V AC (H1 level)
- SERVICE BREAKING CAPACITY (Ics): 66kA at 400/415V AC
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2 (2000A frame)
- MOUNTING TYPE: Fixed
- CONNECTION TYPE: Rear connection
- INTERFACE/CONTROL:
- TRIP UNIT: Micrologic X 2.0 (ULP - Ultra-Low Power)
- PROTECTION FUNCTIONS: Long-time (overload), Short-time, Instantaneous, Ground fault, Neutral protection
- COMMUNICATION: Modbus, Ethernet (via optional communication modules)
- MEASUREMENT: Current, Voltage, Power, Energy, Frequency, Power Factor
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (with front cover), IP20 (without front cover)
- COOLING METHOD: Natural convection
- MOUNTING STYLE: Vertical or horizontal in switchboards
- COMPATIBILITY/APPLICATION: Main incoming protection, sub-distribution, industrial switchboards, data centers, critical power infrastructure, motor control centers.