ОПИСАНИЕ ПРОДУКТА
SCHNEIDER ELECTRIC LVS08254 - Motor Circuit Breaker
The SCHNEIDER ELECTRIC LVS08254 is a TeSys GV4PEM series motor circuit breaker designed for comprehensive motor protection and control in industrial environments. This device integrates electronic trip unit technology to provide precise thermal overload, magnetic short-circuit, phase imbalance, phase loss, and long earth fault protection for three-phase AC motors. It is engineered for direct integration into control panels for applications requiring robust motor safeguarding and operational reliability.
Technical Specifications:
- SERIES/FAMILY: TeSys GV4PEM
- COMPONENT TYPE: Motor Circuit Breaker (MPCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 8A
- POLES: 3P
- OPERATIONAL VOLTAGE: Up to 690VAC
- BREAKING CAPACITY: 50kA at 400/415VAC
- TRIP UNIT TYPE: Electronic
- PROTECTION FUNCTIONS: Thermal overload (adjustable Class 5, 10, 20, 30), Magnetic short-circuit (fixed at 13x In), Phase imbalance, Phase loss, Long earth fault
- MECHANICAL/PHYSICAL:
- CONTROL TYPE: Rotary handle
- MOUNTING: DIN rail or screw mounting
- FORM FACTOR: Compact modular unit
- INTERFACE/CONTROL:
- INDICATORS: Trip indication, auxiliary contacts (optional via external modules)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals)
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Motor protection for industrial machinery, HVAC systems, pumping stations, conveyor systems, and general industrial motor control circuits.
- STANDARDS: IEC 60947-2, IEC 60947-4-1