PEPPERL & FUCHS 087119 - KFD2-SR2-EX1.W.SM Safety Relay / Switch Amplifier
This K-System series intrinsic safety barrier functions as a 2-channel switch amplifier, designed for reliable signal conditioning and safety interlocking in hazardous area applications. It provides galvanic isolation between the safe and hazardous areas, converting signals from NAMUR sensors or mechanical contacts into safe relay outputs for process control and emergency shutdown systems.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2 Series)
- COMPONENT TYPE: Safety Relay / Switch Amplifier (Intrinsic Safety Barrier)
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35V DC
- INPUT: 1-channel for NAMUR sensors (EN 60947-5-6) or potential-free contacts
- OUTPUT: 2 x Normally Open (NO) safety relay outputs, 1 x Normally Closed (NC) fault relay output
- SWITCHING CAPACITY: Max. 250VAC / 2A / 500VA Max. 30VDC / 2A / 60W (resistive load)
- INTERFACE/CONTROL:
- INPUT SIGNAL: Detects open or short circuit line faults on input
- OUTPUT SIGNAL: Relay contacts for switching safety-related circuits
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN rail
- OPERATING TEMPERATURE: -20 to +60 °C
- HAZARDOUS AREA CERTIFICATION: Input suitable for Zone 0, 1, 2 (ATEX, IECEx, UL listed)
- COMPATIBILITY/APPLICATION:
- SAFETY INTEGRITY LEVEL (SIL): Up to SIL 2 (IEC 61508)
- PERFORMANCE LEVEL (PL): Up to PL d (ISO 13849)
- TARGET SYSTEMS: Process control, emergency shutdown (ESD), fire and gas (F&G) systems, machine safety applications requiring intrinsic safety
- TERMINALS: Screw terminals