SCHNEIDER ELECTRIC LVS08836 - Molded Case Circuit Breaker (MCCB)
The SCHNEIDER ELECTRIC LVS08836 is a Compact NSXm series molded case circuit breaker engineered for comprehensive protection and control within low voltage electrical distribution systems. It incorporates a Micrologic 4.2 Vigi electronic trip unit, delivering accurate overload, short-circuit, and integrated earth leakage protection. This device is optimized for critical power distribution, motor feeder circuits, and general circuit isolation in industrial and commercial infrastructure requiring high breaking capacity and advanced fault discrimination.
Technical Specifications:
- SERIES/FAMILY: Compact NSXm
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB), Fixed
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 160A
- POLES: 3P (3-Pole)
- PROTECTION: 3D (3-Protected Poles)
- RATED OPERATIONAL VOLTAGE (Ue): 220-690V AC
- RATED INSULATION VOLTAGE (Ui): 800V AC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED FREQUENCY: 50/60 Hz
- BREAKING CAPACITY (Icu): 36kA at 400/415V AC
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Compact, Fixed
- MOUNTING: Plate or DIN Rail (with adapter)
- CONNECTION: Front terminals (standard)
- INTERFACE/CONTROL:
- TRIP UNIT: Micrologic 4.2 Vigi Electronic Trip Unit
- PROTECTION FUNCTIONS: Long-time (Overload), Short-time, Instantaneous (Short-circuit), Earth Leakage (Vigi)
- ADJUSTMENT: Adjustable long-time (Ir), short-time (Isd), instantaneous (Ii), and earth leakage (Ig) settings
- INDICATION: Trip indication, Earth leakage LED
- COMMUNICATION CAPABILITY: Optional Modbus or Ethernet communication modules via ULP interface
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face, within enclosure)
- POLLUTION DEGREE: 3
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COOLING METHOD: Natural Convection
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Low voltage power distribution, motor protection, generator protection, industrial machinery, building infrastructure, panel boards, switchboards.