OPIS PRODUKTU
SCHNEIDER ELECTRIC METSEPM51HK - PowerLogic PM5100 Series Power Meter
The SCHNEIDER ELECTRIC METSEPM51HK is a PowerLogic PM5100 series power meter engineered for precise measurement and monitoring of electrical parameters in industrial and commercial applications. This device provides essential data for energy management, cost allocation, and basic power quality analysis, integrating seamlessly into existing control and building management systems via standard industrial communication protocols. It is designed for panel mounting in power distribution units, motor control centers, and facility monitoring stations.
Technical Specifications:
- SERIES/FAMILY: PowerLogic PM5000 Series
- COMPONENT TYPE: Power Meter
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE: Up to 480/690V AC L-L (direct connection), 277/400V AC L-N (direct connection)
- NOMINAL CURRENT: 5A (via CTs, primary current dependent on CT ratio)
- MEASUREMENT PARAMETERS: Voltage (L-N, L-L), Current, Frequency, Active Power (P), Reactive Power (Q), Apparent Power (S), Power Factor, Active Energy (kWh), Reactive Energy (kVARh), Apparent Energy (kVAh), Total Harmonic Distortion (THD) for Voltage and Current (up to 15th harmonic)
- ACCURACY: Class 0.5S for Active Energy (IEC 62053-22)
- PHASE CONFIGURATION: 3-phase, 4-wire 3-phase, 3-wire 1-phase, 2-wire 1-phase, 3-wire
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Panel Mount
- DIMENSIONS (FRONT BEZEL): 96mm x 96mm (standard DIN cutout)
- DISPLAY: Backlit LCD
- INTERFACE/CONTROL:
- COMMUNICATION PROTOCOL: Modbus RTU (RS-485)
- DIGITAL INPUTS: 2 (for status monitoring or pulse counting)
- DIGITAL OUTPUTS: 2 (for alarm signaling or control)
- ENVIRONMENTAL/MOUNTING:
- IP RATING (FRONT PANEL): IP52
- IP RATING (REAR TERMINALS): IP20
- COOLING METHOD: Passive
- MOUNTING STYLE: Panel Mount (flush)
- COMPATIBILITY/APPLICATION: Energy Management Systems (EMS), Building Management Systems (BMS), SCADA systems, Power Distribution Monitoring, Cost Allocation, Basic Power Quality Monitoring, Industrial Facility Management.