OPIS PRODUKTU
SCHNEIDER ELECTRIC METSEPM8000SK - Advanced Power Quality and Energy Meter
The SCHNEIDER ELECTRIC PowerLogic PM8000 series is an advanced power quality and energy meter designed for comprehensive electrical network monitoring. This device provides precise measurement of electrical parameters, power quality analysis, and energy consumption data, facilitating robust energy management and operational efficiency in industrial and commercial facilities. It integrates seamlessly into existing control systems for real-time data acquisition and analysis.
Technical Specifications:
- SERIES/FAMILY: PowerLogic PM8000 Series
- COMPONENT TYPE: Advanced Power Quality and Energy Meter
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE: Up to 690V L-L (direct connection), supports higher with VTs
- NOMINAL CURRENT: Requires external Current Transformers (CTs), typically 5A or 1A secondary
- POWER MEASUREMENT: Active (W), Reactive (VAR), Apparent (VA)
- PHASE CONFIGURATION: Single-phase, Three-phase (3P3W, 3P4W)
- FREQUENCY: 50/60 Hz
- ACCURACY CLASS: 0.2S for active energy (IEC 61557-12, IEC 62053-22)
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Panel Mount
- DISPLAY: Integrated graphical display
- INTERFACE/CONTROL:
- COMMUNICATION PROTOCOLS: Modbus TCP/IP, Modbus RTU, ION protocol, BACnet/IP (optional)
- DIGITAL INPUTS: Multiple configurable inputs for status or pulse counting
- DIGITAL OUTPUTS: Multiple configurable outputs for alarms or control
- DATA LOGGING: Onboard memory for historical data, events, and waveforms
- POWER QUALITY ANALYSIS: Harmonics (up to 63rd), sags, swells, interruptions, unbalance
- ENVIRONMENTAL/MOUNTING:
- IP RATING: Front panel typically IP52 or IP65, rear IP30
- COOLING METHOD: Passive convection
- MOUNTING STYLE: Panel mount, 96x96mm DIN cutout compatible
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Energy Management Systems (EMS), Building Management Systems (BMS), SCADA, Industrial Control Systems
- APPLICATIONS: Energy cost allocation, demand management, power quality compliance, facility optimization, critical power monitoring