DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC C25R42D160 - Power Contactor
The SCHNEIDER ELECTRIC C25R42D160 is an industrial power contactor engineered for switching three-phase motor loads and resistive circuits in demanding automation and control applications. This device, part of the TeSys D series, utilizes an electromagnetic coil for remote control of power circuits, providing reliable operational performance for systems requiring load switching up to 25 Amperes. It is suitable for integration into motor control centers, HVAC systems, and general industrial machinery.
Technical Specifications:
- SERIES/FAMILY: TeSys D
- COMPONENT TYPE: Power Contactor
- ELECTRICAL SPECS:
- NOMINAL OPERATIONAL CURRENT (AC-3): 25A at <= 440V
- NOMINAL OPERATIONAL CURRENT (AC-1): 40A at <= 60 degrees C
- NOMINAL OPERATIONAL VOLTAGE: Up to 690VAC
- MOTOR POWER RATING (AC-3): 11kW at 400V, 15kW at 690V
- POLES: 3P (Main Power Circuit)
- AUXILIARY CONTACTS: 1 NO (Normally Open) + 1 NC (Normally Closed) (Integrated)
- CONTROL CIRCUIT VOLTAGE: 230VAC (Standard for TeSys D series specific coil voltage for C25R42D160 should be verified against detailed product documentation)
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6kV
- RATED INSULATION VOLTAGE (Ui): 690V (Power circuit), 600V (Control circuit)
- MECHANICAL/PHYSICAL:
- MOUNTING: 35mm DIN Rail or Screw Mounting
- TERMINALS: Screw Clamp Terminals
- MECHANICAL ENDURANCE: 15 Mcycles
- ELECTRICAL ENDURANCE (AC-3): 1.6 Mcycles
- INTERFACE/CONTROL:
- CONTROL TYPE: Electromagnetically Actuated
- COIL CONSUMPTION (INRUSH): 70VA at 230VAC
- COIL CONSUMPTION (SEALED): 7.5VA at 230VAC
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Front Face)
- OPERATING TEMPERATURE: -5 to 60 degrees C
- STORAGE TEMPERATURE: -60 to 80 degrees C
- ALTITUDE: Up to 3000m without derating
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Motor control (AC-3), Resistive loads (AC-1), Switching of power circuits, Industrial automation, HVAC systems, Pumping applications, Conveyor systems.
- COMPATIBILITY: Compatible with TeSys D thermal overload relays, auxiliary contact blocks, and other TeSys control components.