DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC LV848212 - Air Circuit Breaker
SCHNEIDER ELECTRIC LV848212 is a MasterPact MTZ2 series fixed air circuit breaker, engineered for robust electrical distribution protection in demanding industrial environments. It integrates an advanced Micrologic 5.2 E electronic trip unit, providing comprehensive overload, short-circuit, and instantaneous fault protection. This device is specifically designed for critical power infrastructure, ensuring reliable circuit isolation and system integrity in main incoming and sub-distribution applications.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 2000A (Frame Size)
- POLES: 3P
- BREAKING CAPACITY (Icu/Ics): 65kA at 400/415VAC
- OPERATIONAL VOLTAGE (Ue): 690VAC Max
- INSULATION VOLTAGE (Ui): 1000VAC
- IMPULSE WITHSTAND VOLTAGE (Uimp): 12kV
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Fixed Type
- FRAME SIZE: MTZ2
- MOUNTING: Panel-mounted
- INTERFACE/CONTROL:
- TRIP UNIT: Micrologic 5.2 E Electronic Trip Unit
- PROTECTION FUNCTIONS: Long Time (Overload), Short Time (Short-circuit), Instantaneous
- MEASUREMENT CAPABILITIES: Current (RMS)
- COMMUNICATION: Modbus-ready (requires optional communication module)
- AUXILIARY CONTACTS: Standard configuration includes auxiliary and fault indication contacts
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (Front face with door), IP30 (Without door)
- COOLING METHOD: Natural Convection
- OPERATING TEMPERATURE: -25°C to +70°C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Main incoming protection, sub-distribution, generator protection, large motor protection
- APPLICATIONS: Industrial switchboards, data centers, commercial building power distribution, critical infrastructure