SCHNEIDER ELECTRIC LVS04264 - Molded Case Circuit Breaker
The SCHNEIDER ELECTRIC LVS04264 is a ComPact NSXm series molded case circuit breaker (MCCB) designed for effective electrical circuit protection and isolation in low voltage distribution systems. Featuring a 4-pole configuration and a 160A nominal current rating, this device integrates a Micrologic 4.1 electronic trip unit to provide accurate overload, short-circuit, and ground fault protection. It is engineered for demanding applications in industrial panels, motor control centers, and building infrastructure requiring consistent power distribution and equipment safeguarding.
Technical Specifications:
- SERIES/FAMILY: ComPact NSXm
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 160A
- NUMBER OF POLES: 4P
- BREAKING CAPACITY (Icu): 36kA at 400/415V AC, 50/60 Hz (N-type)
- NOMINAL OPERATIONAL VOLTAGE (Ue): 220/240V AC to 660/690V AC
- NOMINAL INSULATION VOLTAGE (Ui): 800V AC
- FREQUENCY: 50/60 Hz
- TRIP UNIT TYPE: Electronic
- TRIP UNIT MODEL: Micrologic 4.1
- PROTECTION FUNCTIONS: Long-time (overload), Short-time (selective short-circuit), Instantaneous (short-circuit), Ground Fault
- MECHANICAL/PHYSICAL:
- FRAME SIZE: NSXm 160
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: EverLink Power Terminals
- FORM FACTOR: Compact, modular design for panel integration
- INTERFACE/CONTROL:
- FEEDBACK: Local LED indicators for trip status and overload pre-alarm
- COMMUNICATION PROTOCOLS: Not inherently equipped with communication protocols (Micrologic 4.1)
- AUXILIARY COMPATIBILITY: Supports optional auxiliary contacts, shunt trips, undervoltage releases
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face with escutcheon), IP20 (terminals)
- POLLUTION DEGREE: 3 (IEC 60947-1)
- OPERATING TEMPERATURE RANGE: -25 to 70 °C
- MOUNTING STYLE: DIN rail or mounting plate
- COMPATIBILITY/APPLICATION:
- STANDARDS COMPLIANCE: IEC 60947-2
- TARGET APPLICATIONS: Low voltage power distribution, industrial machinery protection, commercial building infrastructure, motor control centers