ОПИСАНИЕ ПРОДУКТА
KEYENCE FD-M100ATP - Digital Clamp-On Flow Sensor Main Unit
This unit is a digital main unit for the KEYENCE FD-M series clamp-on flow sensors, engineered for non-contact measurement of liquid flow rates in industrial environments. It provides signal processing, real-time digital display, and configurable output capabilities, facilitating precise monitoring and control in fluid management, process automation, and equipment diagnostics. The system operates on an ultrasonic measurement principle, ensuring non-invasive flow detection.
Technical Specifications:
- SERIES/FAMILY: FD-M Series
- COMPONENT TYPE: Digital Clamp-On Flow Sensor Main Unit
- ELECTRICAL SPECS:
- POWER SUPPLY: 24 VDC +/-10%
- CURRENT CONSUMPTION: 150 mA (max, excluding sensor head)
- INTERFACE/CONTROL:
- ANALOG OUTPUT: 1x 4-20 mA or 0-10 V (selectable)
- DISCRETE OUTPUTS: 2x PNP Open Collector Transistor Outputs (configurable for alarm, totalizer, etc.)
- EXTERNAL INPUTS: 2x (e.g., zero reset, flow rate display hold)
- DISPLAY: 7-segment, 4-digit LED display with sub-display
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP65 (front panel when panel mounted, IP20 for rear terminal block)
- OPERATING TEMPERATURE: -10 to +50 degrees C (14 to 122 degrees F)
- MOUNTING STYLE: DIN rail mount or panel mount
- COMPATIBILITY/APPLICATION:
- SENSOR HEAD COMPATIBILITY: Designed for use with KEYENCE FD-MA series clamp-on sensor heads (e.g., FD-MA100 for DN25-DN100 pipes)
- MEASUREMENT MEDIUM: Various conductive and non-conductive liquids (water, oils, chemicals, coolants)
- TARGET APPLICATIONS: Fluid management, process monitoring, pump control, HVAC systems, cooling water lines, chemical dosing.