ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 087721 - Isolated Barrier - Frequency Converter and Switch Amplifier
The PEPPERL & FUCHS KFD2-CD-EX1.32 is an intrinsically safe isolated barrier from the K-System series, engineered for converting and switching frequency signals from NAMUR sensors or dry contacts in hazardous environments. It provides galvanic isolation between the input, output, and power supply, ensuring signal integrity and safety compliance for critical process automation applications. This module integrates both frequency conversion to an analog current output and dual relay switching capabilities for comprehensive signal processing.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2-CD-EX1.32)
- COMPONENT TYPE: Isolated Barrier, Frequency Converter and Switch Amplifier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20 to 35 VDC
- POWER CONSUMPTION: < 1.5 W
- INPUT: NAMUR sensor (EN 60947-5-6) or dry contact, 0 Hz to 10 kHz frequency range
- OUTPUT 1 (SWITCH): 2 x Relay outputs, normally open (NO) or normally closed (NC) configurable, max. 250 VAC / 2 A or 125 VDC / 2 A
- OUTPUT 2 (ANALOG): 1 x Current output, 0/4-20 mA, configurable for frequency conversion
- INTERFACE/CONTROL:
- CONFIGURATION: DIP switches for basic settings, PACTware FDT/DTM for advanced configuration
- DIAGNOSTICS: Line fault detection (LFD) for sensor circuit
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35 mm DIN rail
- OPERATING TEMPERATURE: -20 to +60 °C (-4 to +140 °F)
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, cULus for intrinsic safety (e.g., [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex nA nC] IIC T4 Gc)
- COMPATIBILITY/APPLICATION:
- APPLICATION: Intrinsic safety interface for frequency signals, speed monitoring, flow measurement, position detection in hazardous areas (Zone 0, 1, 2)
- INPUT COMPATIBILITY: NAMUR proximity sensors, mechanical contacts
- OUTPUT COMPATIBILITY: PLCs, DCS, safety instrumented systems