PEPPERL & FUCHS 088834 - Intrinsic Safety Barrier, Solenoid Driver
This intrinsic safety barrier from the K-System KFD2 series is engineered for the safe control of field devices situated in hazardous areas. It functions as a switch amplifier and solenoid driver, providing a galvanically isolated, intrinsically safe output for actuating solenoid valves, alarms, or LEDs from a safe area control system. The module integrates line fault detection to ensure system integrity and compliance with international explosion protection standards.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Intrinsic Safety Barrier, Switch Amplifier, Solenoid Driver
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35V DC (Nominal 24V DC)
- INPUT: Digital input from safe area control system (e.g., PLC output)
- OUTPUT: Intrinsically safe voltage output to hazardous area
- OUTPUT VOLTAGE: 24V DC
- OUTPUT CURRENT: Max. 40mA
- INTERFACE/CONTROL:
- INPUT SIGNAL: Switch or transistor output
- OUTPUT SIGNAL: Switched voltage for inductive or resistive loads
- DIAGNOSTICS: Line fault detection (LFD) for open or short circuit in field loop
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN-rail mount
- OPERATING TEMPERATURE: -20 °C to +60 °C
- COMPATIBILITY/APPLICATION:
- HAZARDOUS AREA CLASSIFICATION: Zone 0, 1, 2 (gas) Zone 20, 21, 22 (dust)
- TARGET DEVICES: Solenoid valves, alarms, LEDs, contactors in hazardous locations
- CERTIFICATIONS: ATEX, IECEx, UL, cUL, FM, KOSHA (standard for this product line)