ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 101915 - KFD2-CD-EX1.32 Intrinsic Safety Barrier
The PEPPERL & FUCHS KFD2-CD-EX1.32, identified by order code 101915, is a K-System intrinsic safety barrier designed for controlling devices in hazardous locations. This single-channel switch amplifier provides galvanic isolation and energy limitation to safely operate solenoids, sounders, or LEDs within Zone 0, 1, or 2 environments, ensuring compliance with international explosion protection standards.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Intrinsic Safety Barrier, Switch Amplifier, Solenoid Driver
- ELECTRICAL SPECS:
- NOMINAL SUPPLY VOLTAGE: 24 VDC (19.2 VDC to 30 VDC operating range)
- POWER CONSUMPTION: < 1.5 W
- INPUT: 1x Digital Input (from safe area control system)
- OUTPUT: 1x Intrinsically Safe Output
- OUTPUT CHARACTERISTICS: Uo = 25.2 V, Io = 93 mA, Po = 580 mW (for hazardous area load)
- INTERFACE/CONTROL:
- SIGNAL TYPE: Digital control input, intrinsically safe output for resistive and inductive loads
- DIAGNOSTICS: Line fault detection (short circuit, wire break)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN-rail
- OPERATING TEMPERATURE: -20 °C to +60 °C
- EXPLOSION PROTECTION: ATEX, IECEx, FM, cULus certified for Zone 0, 1, 2 (gas) and Zone 20, 21, 22 (dust) applications
- COMPATIBILITY/APPLICATION:
- TARGET APPLICATIONS: Process automation, chemical, oil & gas, pharmaceutical industries
- LOAD TYPES: Solenoid valves, alarm beacons, LEDs, sounders in hazardous areas